Products:
Boiler Room Products: Blowdown Tanks
Blowdown Tanks
Specification
Note: items shown in parenthesis () are options.
Blowdown Tank shall be Model __________ as
manufactured by Precision Boilers. The pressure vessel shall
be designed for 50 PSI and shall meet the applicable requirements
for ASME Section VIII, U-stamped, and National Board Registered.
The manufacturer shall provide the owner with a copy of the
Manufacturer's Data Report. The Tank shall have ______ gallon
capacity (total volume), _____ (NPT) (FLG) tangential inlet with
wear plate, and properly sized (per National Board recommendations)
vent, outlet and outlet restricting orifice. The tank outer
surface shall be painted with one coat of industrial grade red oxide
primer.
Specifications subject to change without notice.
|
   
|
|
|
|