1. General
Furnish and install as shown on the plans a PRECISION Storage Water
Heater Model FPW-_____which shall be a complete pretested, packaged
unit consisting of a (gas) (oil) power burner with integral heat
exchanger and hot water storage vessel, complete with all required
operating and safety controls. Each heater shall have a (nominal)
(actual) storage capacity of ______gallons.
The complete heater shall be UL labeled and shall include a pressure
vessel built to the requirements of ASME Section IV, designed for
(125) (150) PSIG, and National Board registered. A copy of the
Manufacturer's Data Report shall be provided to the owner.
2. Power Burner (Select One)
A. Gas-Fired Burner with a recovery capacity of ____ GPH water from
____F to ____F, with an input of _____BTU/H (natural gas) (propane).
B. Oil-Fired Burner with a recovery capacity of ____GPH water from
____F to _____F, with an input of ____BTU/H (#1) (#2) fuel oil.
C. Gas-Oil Combination Burner with a recovery capacity of _____GPH
water from _____F to _____F, with an input of ____F BTU/H (natural
gas) (propane) and ____F (#1) (#2) fuel oil.
3. Controls and Safety Devices
Each heater shall be equipped with an ASME pressure and temperature
relief valve(s) , separate pressure and temperature gauges,
temperature control, upper temperature limit (auto reset), upper
temperature limit (manual reset), low water cutoff (manual reset
wltest button and pilot light), and drain valve.
4. Burner Controls
A. Natural or Propane
Gas
120V control power with 24V combustion control, redundant gas valves,
flame rod sensor with 4 sec safety shutdown, 30 see prepurge,
combustion air proving switch, direct spark ignition with 7300V
ignition transformer, 3200 RPM motor. Burner to have primary air
adjustment (with) (without) optional outside air intake adapter.
B. Oil
120V control power with 3500 RPM fuel pump, cadmium sulfide cell and
relay control, 10,000V constant duty ignition transformer, solenoid
oil valve(s). Burner to have primary air adjustment (with) (without)
optional outside air intake adapter.
5. Enclosure
The pressure vessel shall be insulated with a minimum of 4 inches of
3/4 pound density fiberglass insulation (or equivalent) and shall be
enclosed in an enameled sheet steel enclosure. The assembly shall
conform to heat loss requirements of ASHRAE 90 and ANSI Z21.1 0.3.
6. Vessel Lining
Heat exchanger shall utilize copper clad firetubes, with a min copper
thickness of 0.04", and storage vessel shall be lined with (PRECISION
SEAL) (Copper Coat™) (Nickel Coat) (Cement) as follows:
(Insert one of the
following paragraphs that applies to your selection of linings)
6.1 Seal:
The tank interior shall be lined with two separate coats of
polymerized epoxy to a dry film thickness of 5-6 mils per coat. Each
coat shall be baked and force-cured in an oven.
6.2 Copper Coat:
The tank interior shall be lined with 100% dead soft copper by using
the "Thermometalization Process", creating a non-ferrous,
corrosion-resistant protective surface. In addition, the tank shall be
equipped with a Copper CoaFM manway cover and Copper CoatTM threaded
tank openings. The copper shall then be overcoated with two (2)
separate coats of Precision Seal to a dry thickness of 10 - 12 mils.
6.3 Cement Lined:
The tank interior shall be completely lined with aluminum silicate
cement, good for service temperatures to 250°F with the same
coefficient of expansion as medium steel. The cement is applied at a
minimum thickness of 5/8" to form a hard one-piece lining.
Specifications subject to change without notice.
|