Products:
Electric: HVJ
Model HVJ High Voltage Electrode Boiler
Specification
SPECIFICATION FOR
HIGH VOLTAGE ELECTRODE STEAM BOILERS
Model ________________ ( ______ KW )
Job Name: __________________________________________
Provide PRECISION High Voltage Electrode-Type Steam Boilers as
manufactured by PRECISION Boilers, Inc, Morristown, TN for operation
on _____ volts, 3 phase, 4-wire, ____ cycle AC. Boiler shall be
rated ________ max KW, shall be designed for ____psi, and shall be
operated at ____ psig nominal steam pressure.
1.0 GENERAL
The boiler shall be built to ASME Code Section I, Part PEB, and
shall consist of a pressure vessel having a central column (header)
from which water flows through nozzles toward the electrodes which
surround the header. Steam is generated from the surface of the
streams of water flowing to the electrodes due to heat generated, in
proportion to the water's conductance, as the electrical current
flows through the water. Steam is similarly produced in the excess
streams of water as it falls from the electrodes downward to the
counter electrode (fixed neutral).
Regulation of the boiler output shall be accomplished by controlling
the water level in the nozzle header so that a greater or smaller
number of nozzles are supplied with water, and thus, a greater
amount of water comes into contact with the boiler electrodes.
Control of this water level, in turn, is accomplished by varying,
via the variable speed circulation pump(s), the water flow to the
header in accordance with the respective boiler control -- either to
maintain the desired steam pressure or to prevent the boiler from
drawing more than the desired kilowatts when the steam requirements
exceed the KW setpoint. The boiler electrodes shall be located
entirely in the boiler steam space so that stopping of the boiler
circulation pump will automatically effect boiler shut-down.
2.0 COMPONENT PARTS
2.1 Boiler Shell
The boiler shall consist of a single vertical vessel constructed and
stamped in accordance with the ASME Boiler and Pressure Vessel Code,
Section VIII, and shall be National Board inspected with a
Manufacturer's Data Report provided. The vessel shall be designed
and stamped for a maximum operating pressure of ____ psi for
operation at ____ psig.
The boiler vessel shall be fabricated of ASTM SA515-70 or SA516-70
steel. A 12" x 16" manhole shall be provided for access to the
boiler interior for internal inspection and repair or replacement of
internal parts. All boiler connections greater than 2" pipe size
shall be flanged; and all steam connections shall be made to the
vertical portion of the vessel to preclude the possibility of
leaking steam in the proximity of high voltage electrode
terminations. The vessel inner surface shall in-corporate a di-electric
barrier above the water level to eliminate foam-induced arcing.
2.2 Central Column Nozzle Header
The central column, through which water is supplied to the nozzles,
shall be fabricated of mild steel and shall be supported from the
top of the boiler. The jet nozzles shall be in vertical rows and
mounted flush with the external surface of the header. Nozzles shall
be located so as to maintain uniform phase loadings at all levels of
water in the nozzle header. Nozzles shall be free of vanes, to
facilitate cleaning.
2.3 Load Regulation
Load regulation shall be accomplished by controlling water flow to
the header by VFD of the circu-lation pump(s) operated from the
boiler control system. The VFD(s) shall either be located in the
boiler control cabinet or in proximity of the circulation pump(s),
dependent on the job require-ments.
2.4 Boiler Circulating Pump(s)
The boiler circulating pump(s), located inside the pressure vessel,
shall be mixed-flow centrifugal type rated for continuous duty at
the boiler operating pressure and temperature, and shall be
de-signed for compatibility with low NPSH. The pump shall
incorporate a double mechanical seal with water cooling, and shall
be removable from outside the vessel. The pump motor shall be
3-phase, ____ cycle, rated for inverter duty, and shall be sized for
100% of maximum pump horsepower requirements, (ie, with cold water
at full flow).
2.5 Electrodes
Boiler electrodes shall be of mild steel construction, with
replaceable electrode strike plates, and shall be supported by
insulators of high grade porcelain. The electrodes shall incorporate
dielectric barriers on non-conductive surfaces to eliminate
spray-induced arcing. The insulators on the steam side shall be
protected from flowing steam by throttling shields. Critical
surfaces of the porcelain shall be metallized, and shorting clips
shall be used to bridge all air gaps. Steam leak-age paths shall be
provided to indicate the condition of the insulator sealing gaskets.
2.6 BOILER CONTROL SYSTEM
2.6.1 Pressure and Load Controls
The boiler control system shall incorporate both pressure control
and current load control in the primary control system in a manner
which will permit the boiler to maintain the desired steam pressure
so long as the steam demand does not exceed a set maximum KW limit;
and, at such times as the demand exceeds this set limit, the control
shall regulate the boiler output to this maximum. The maximum
allowable KW output shall be adjustable by the operator, either
locally or remotely, through a range of 0 to 100% of the maximum
rated output; and the boiler shall also regulate from 0 to 100% of
the maximum rated output as required by the pressure control.
Unless otherwise specified, the control system shall be via PLC with
a Touchscreen HMI. The PLC shall include a modem and shall also be
able to communicate with the Customer’s DCS/BAS processor as
required. System shall be Siemens, or AB at a premium cost.
2.6.2 Load Shed Option
A load shedding circuit, which will operate in conjunction with
either a central or local load pro-grammer system, is available as
an option.
2.6.3 Limit Controls
The boiler shall be equipped with limit controls to shut down the
boiler in the event of occurrence of any of the following
conditions:
(1) excess pressure; (2) low water; (3) high water.
In addition, high conductivity and loss of circulation pump cooling
water shall be alarmed. Limit controls, such as supervisory relays,
overcurrent or ground fault relays (supplied by others), may be
connected into the limit control circuit.
2.6.4 Water Level Control
The boiler water level control shall be a single element system
incorporated into the boiler master PLC which will operate a
normally closed control valve in the feedwater supply line to
maintain the flow of feedwater in proportion to the drum water
level. Unless otherwise specified, the water level control system
shall incorporate a level transmitter, and shall operate a Cashco,
Fisher, or equal, pneumatic valve.
2.6.5 Conductivity Control
Conductivity of the water being circulated to the boiler electrodes
shall be controlled by an indicat-ing-type conductivity controller
which will continuously measure/indicate the conductivity of the
water via a bleed off the circulating pump discharge. All water
flowing to the conductivity cell will be returned to the boiler to
effect minimal energy loss.
Means for isolation of the conductivity cell shall be provided so
that normal cell maintenance can be performed with the boiler in
operation.
The control will have separately adjustable high and low set points.
On actuation of the "high" set point, an automatic boiler blowdown
cycle will begin and the HMI will indicate that bleed is in process.
Actuation of the "low" contact will be indicated on the HMI and may
be used either to sound an alarm or to initiate a chemical feed
cycle (neither alarm nor chemical feed pump is sup-plied as standard
equipment with the boiler). The conductivity control shall be
Rosemount, and shall include the proper conductivity measuring cell.
2.7 BOILER ACCESSORIES
The boiler shall be supplied with the following necessary equipment:
2.7.1 Water Column
A water column shall be provided and shall be suitable for mounting
of the water sight gauge and the high and low water cutoffs. A water
column drain valve will be provided. The water column connection to
the boiler shall be 1" pipe size minimum. The cutoff switches shall
be independent of the level control system.
2.7.2 Safety Valves
The boiler will have a minimum of two safety valves, each mounted on
a nozzle extending from the vertical portion of the boiler drum.
Each valve shall be ASME rated and stamped. Aggregated capacity of
the safety valves at their set pressure will not be less than 3.5
pounds per hour per KW input.
2.7.3 Back Pressure Regulating Valve
A back pressure regulating valve will be supplied for installation
on the steam outlet of the boiler, and shall be set to control
pressure at approximately 5% below normal operating pressure in the
event that the steam requirement exceeds boiler output. Control of
the back pressure regulating valve shall be incorporated into the
boiler master PLC.
2.7.4 Other Accessories
Other accessories in the standard boiler package include:
Standby heater rated ____ KW (____/3/___), steam pressure gauge,
boiler water temperature gauge, feedwater stop valve, check valve
and 3-valve bypass, one slow-opening and one quick-opening blowdown
valves, auto and manual air release valves, steam outlet non-return
stop and check valves, steam outlet gate valve with 1” free-blow
vent valve, sample cooler, bypass feeder (for electrolyte), and
circulation pump cooling water flow switch(es).
2.8 INSULATION, CASING AND TERMINAL GUARDS
The boiler shall be insulated with 4" of foil-faced glass fiber
insulation secured to the boiler to pre-vent sagging.
Boiler casing will be 16 gauge steel panels secured to the boiler by
means of supports welded to the boiler shell. The boiler high
voltage terminals will be enclosed in a protective screen enclosure
with "Type D" Kirk-Key interlocks on the access openings to prevent
entrance unless the boiler supply switchgear is locked open.
2.9 CONTROL PANEL
The electrical control relays, circulating pump VFD(s), standby
heater contactor(s), ____V disconnect and associated push buttons,
lights, voltmeter, wattmeter, ammeters (3), and other compo-nents of
the boiler control system shall be mounted and prewired in a
floor-standing Nema 12 cabinet which will be finished to match the
boiler. Control shall be via PLC with a Touchscreen HMI, and should
include a UPS to assure continuous operation of the control system
during mo-mentary power outages. The control system shall include a
telephone jack and modem, as well as communication ports (eg, RS232,
RS485, Ethernet, etc) as required for communication with a central
DCS/BAS processor. The PLC shall be Siemens, or AB at a premium
cost.
Control cabinet wiring shall be of 16 ga stranded copper wire, and
shall be color coded. Terminal blocks shall be Marathon or equal;
starters, contactors, disconnects, control relays, pilot lights, and
pushbuttons shall be Siemens, ABB, or equal; meters shall be
switchboard class GE, Yew, Multitek, or Electro Ind. All safety
controls shall be in an energized condition during normal boiler
operation.
3.0 BOILER ERECTION
The boiler will be shipped partially assembled and will require some
field assembly, and comple-tion of electrical, pneumatic and piping
connections. The boiler manufacturer shall furnish an erection
engineer to supervise the assembly, connection and start-up of the
boiler.
Labor and material (except for boiler components) required for
erection of the boiler are to be fur-nished by others.
4.0 ELECTRICAL SUPPLY SYSTEM
The boiler will require a 3-phase, 4-wire supply circuit from a wye-connected
transformer with the transformer neutral solidly grounded at the
transformer and extended by means of a full size insu-lated (600 V)
conductor to the boiler neutral lug. The boiler enclosure and
control cabinet shall be grounded to the building ground system via
property sized equipment grounds. Unless otherwise specified, the
motor of the boiler circulating pump and the standby heater will be
____/3/___; and the boiler control circuits will be ____/1/___ from
either an external power supply or from a ___/___ control
transformer located in the control panel. A 20A ____/1/___ lighting
circuit shall be provided to supply lighting and a convenience
outlet within the control cabinet.
4.1 High Voltage Switchgear
High voltage switchgear for the boiler supply circuit is to be
furnished by others, unless otherwise specified. The switchgear
should be a stored energy type rated for the boiler voltage and
ampere load, and should be equipped to protect both the branch and
feeder circuits, as required, and to protect the boiler from
instantaneous overcurrent. The switchgear should also incorporate
remote tripping, so it can be opened by the boiler limit controls
for safety shutdown, and remote closing, so that the operator can
conveniently close the breaker. PT’s, CT's, and an auxiliary switch
shall also be provided for use in the boiler control circuit.
NOTE: Fused disconnects or air-magnetic breakers are not recommended
for this service.
5.0 CONDENSATE RETURN SYSTEM
The boiler condensate return system, including deaerator and feed
pump(s), is to be furnished by others, unless otherwise specified.
6.0 ELECTROLYTE FEED SYSTEM
The boiler shall be supplied with a 4-valve bypass/shot feeder
connected in the feedwater line to the boiler to effect electrolyte
feed at startup. An automatic electrolyte feed system may also be
included and if so shall be furnished by others, unless otherwise
specified.
7.0 FEEDWATER TREATMENT
Feedwater treatment equipment, if needed, is to be furnished by
others. Feedwater hardness lim-its shall be based on a feedwater
analysis and the percent of makeup water required. Conductiv-ity
required for the water in the boiler to enable full load operation
will be in the 1400 to 2200 mi-cromho/cm range. Feedwater
conductivity, however, is recommended at less than 50 mi-cromho/cm
for efficient boiler operation, unless blowdown losses can be
economically recovered via heat exchangers.
|
   
|
|