Electric: Model HW Series II
Model HW Series II Hot Water Boiler
Specification
1.
General
Furnish and install
as shown on the plans ____ electric hot water boilers, fabricated per
these specifications, including all accessories and construction
features as described herein. Boilers shall be completely factory
assembled and pre-tested prior to shipment. Boilers shall be UL
labeled and shall include an ASME Section IV pressure vessel which has
been fabricated under inspection by an authorized inspector holding a
National Board commission and subsequently stamped and National Board
registered. Units greater than 117 KW shall also comply with CSD-1.
2. Ratings
Boilers shall each
be PRECISION “Series II’ Model No. HW____-_____ rated _____KW,
designed and fabricated for a balanced 3-phase, 3-wire, delta load at
____volts, 3-phase, ___hertz. The boilers shall be designed for ____GPM
with a discharge temperature of _____ °F with entering water at
________°F.
3. Pressure Vessel
The pressure vessel
and all trim shall be as set forth in the ASME Code, including ASME "HV"
stamped safety relief valve sized as required. The vessel shall be
provided with a threaded 3" (4" flanged) inlet, a threaded 3" (4"
flanged) outlet, plus safety valve and drain nozzle as required. The
pressure vessel shall be housed in a 16-gauge steel enclosure showing
4 inches of 3/4 pound-density fiberglas insulation. The electric
panel and vessel shall be mounted on a common, structural steel base
with overall dimensions of the unit not to exceed ____" D x ___" W x
52" H.
4. Internal Power Distribution
The power
distribution shall be through cable connection to mechanical lugs.
Power shall be fed through current limiting fuses to magnetic
contactors, and then to the heating element circuits. Contactors
shall be 3-pole magnetic contactors tested by UL for 500,000 cycles at
full load. The coil voltage shall be 120-volts Internal wiring shall
be in accordance with UL & NEC.
5. Heating Elements
Elements shall be
individually mounted in steel flanges. The flange size shall not
exceed 2 1/2 inches square, with a maximum of three single-bend
U-shaped element blades per flange. Element sheath material shall be
Incoloy; element watt density shall be 75 WSI.
6. Controls
The control circuit
shall be 120-volt single-phase, one side grounded. Control voltage
shall be provided by an integral control circuit transformer, fused on
both legs of the primary, with a control circuit fuse on the
ungrounded leg of the secondary. The controls shall include an ON/OFF
switch, preheat (manual limit) switch (above 240KW), solid state step
control (_____ steps), indicator lights for each stage of heating, a
low water cut-off, and one auto reset and one manual reset high limit
temperature switches.
7. Manufacturer
Boilers shall be
PRECISION Model HW_____-______or approved equivalent. Alternate bids
shall indicate any deviations from these specifications, and shall
state price additions or deductions for substitution of said
alternates.
Specifications subject to change without notice.
|