Products:
Electric: ISH
Model ISH/IAH/IOH/IWH Instantaneous Circulation Superheaters
Specification
1. General
Furnish and install as shown on the plans one
(1) PRECISION model ISH (Steam), IAH (Air), IOH (Oil) or IWH (Water)
instantaneous circulation heater, model number __________________.
2. Pressure Vessel, Heater, Mounting & Control Cabinet
Vessel shall be constructed and stamped in accordance with ASME
Section IV, H stamped (water) or Section VIII, U stamped (Steam),
and National Board registered. The heater shall comply with NEC and
UL requirements. IAH/IOH/IWH heaters shall be wrapped with 4” of
fiberglass insulation. ISH heaters shall be wrapped in 2” of
Rockwool insulation with on layer of standard 2” fiberglass
insulation drapped over top of the vessel and extended down its
side.
Single-chamber units shall be shipped _______________ (insulated and
sheet metal mounted for floor mounting or uninsulated for pipeline
mounting). Multi-chamber units shall be mounted on a common base and
shipped insulated with a sheet metal enclosure and an integral
control cabinet.
3. Heating Elements
Incoloy or copper sheathed heating elements shall be flange mounted
via compression fittings in the ASME code pressure vessel. Elements
must be replaceable by using standard tools. Element watt density
and sheath material shall be selected to best suit the requirements
of each application.
4. Electronic Controls
The electronic control scheme shall include
Proportional/Integral/Derivative (PID)-controlled input. Elements
shall be ________ (step or 0-100% SCR Power Controlled).
5. Control Panel
A NEMA _____ (4 or 1) control panel, or 14 gauge control enclosure,
shall be __________ (mounted with the heater on a common skid or as
part of the heater enclosure, or shipped for ______ (wall or floor)
mounting).
6. Miscellaneous
All units shall comply with the appropriate drawing(s) and written
specifications.