Model PCW — Compac™ Electric Hot Water Boiler
Specification
1. General
Furnish and install as shown on the plans ____
electric hot water boilers, fabricated per these specifications,
including all accessories and construction features as described
herein. Boilers shall be completely factory assembled and
pre-tested prior to shipment. Boilers shall be UL/ULC labeled and
shall include an ASME Section IV pressure vessel which has been
fabricated under inspection by an authorized inspector holding a
National Board commission and subsequently stamped and National
Board registered. Units greater than 117 KW shall also comply
with CSD-1.
2. Ratings
Boilers shall each be PRECISION Compac Model No.
PCW-1, 2, 3, 4, or 5 rated _____KW, designed and fabricated for a
balanced 3-phase, 3-wire, delta load at ____volts, 3-phase,
___hertz. The boilers shall be designed for ____GPM with a
discharge temperature of _____ °F.
3. Pressure Vessel
The pressure vessel and all trim shall be as set
forth in the ASME Code, including ASME "HV" stamped safety relief
valve sized as required. The vessel shall be provided with a
threaded 3" (4" flanged) inlet, a threaded 3" (4" flanged) outlet,
plus safety valve and drain nozzle as required. The pressure
vessel shall be housed in a 16-gauge steel enclosure showing 4
inches of 3/4 pound-densith fiberglas insulation. The electric
panel and vessel shall be mounted on a common, structural steel base
with overall dimensiona of the unit not to exceed ____" D x ___" W x
52" H.
4. Internal Power Distribution
The power distribution shall be through cabel
connection to mechanical lugs. Power shall be fed through current
limiting fuses to magnetic contactors, and then to the heating
element circuits. Contactors shall be 3-pol magnetic
contactors tested by UL for 500,000 cycles at full load. The
coil voltage shall be 120-volts Internal wiring shall be in
accordance with UL & NEC.
5. Heating Elements
Elements shall be individually mounted in steel
flanges. The flange size shall not exceed 2 1/2 inches square,
with a maximum of three single-bend U-shaped element blades per
flange. Element sheath material shall be Incoloy.
6. Controls
The control circuit shall be 120-volt
single-phase, one side grounded. Control voltage shall be provided
by an integral control circuit transformer, fused on both legs of
the primary, with a control circuit fuse on the ungrounded leg of
the secondary. The controls shall include an ON/OFF switch, a
manual limit switch and indicator light for each stage of heating, a
low water cut-off, and one auto reset and one manual reset high
limit temperature switch.
7. Manufacturer
Boilers shall be Precision Model PCW-1, 2, 3, 4,
or 5 or approved equivalent. Alternate bids shall indicate any
deviations from these specifications, and shall state price
additions or deductions for substitution of said alternates.