Model ST Series II Electric Steam Boiler
Dimensional Data
Components
Physical Data
(1) Model Number
Max Input KW
Steam F&A 212F (PPH)
Max # of Elements
Connection Sizes
Tank Data
Dimensions (2)
(Inches)
Weight (Pounds)
Feed Water
Blowdown
Steam Outlet
15PSI
>15 PSI
15PSI
50PSI
150PSI
Dims (In)
Vol (Gal)
L(3)
W
H
H'
Ship
Oper
ST12S-
60
205
3
1/2"
3/4"
3/4"/1"
1-1/4"
1"
3/4"
12x42
20
50
28
22
25
550
650
ST16S-
140
476
7
1/2"
3/4"
3/4"/1"
2"
1"
3/4"
16x42
32
50
32
26
33
750
910
ST15D-
200
682
10
1/2"
3/4"
3/4"/1"
2"
1-1/4"
3/4"
16x42
32
54
32
26
33
800
960
ST20S-
240
819
12
3/4"
1"
1"
2-1/2"
1-1/4"
1"
20x42
41
50
36
30
51
1000
1200
ST20D-
320
1092
16
3/4"
1"
1"
3"
1-1/2"
1"
20x42
41
54
36
30
51
1050
1250
ST24S-
360
1228
18
3/4"
1-1/4"
1"
4" FLG
1-1/2"
1-1/4"
24x44
74
52
40
34
51
1300
1670
ST24D-
600
2047
30
3/4"
1-1/4"
1"
6" FLG
2"
1-1/2"
24x44
74
56
40
34
51
1400
1770
ST30D-
960
3276
48
3/4"
1-1/2"
1"
6" FLG
3" FLG
2"
30x46
124
60
48
40
63
1700
2340
ST36D-
1280
4367
64
1"
1-1/2"
1"
6" FLG
3" FLG
2"
36x46
166
60
54
46
63
2100
2960
ST42D-
1880
6415
94
1"
1-1/2"
1"
8" FLG
4" FLG
3" FLG
42x48
230
64
62
52
81
2800
4000
ST48D-
2400
8325
122
1"
2"
1-1/4"
8" FLG
5" FLG
3" FLG
48x54
345
70†
68
58
87
4600
6300
ST54D-
3040
11598
152
1-1/4"
2"
1-1/4"
10" FLG
6" FLG
4" FLG
54x60
500
76†
74
66
89
5600
8100
ST60D-
4000
13640
200
1-1/4"
2"
1-1/2"
10" FLG
6" FLG
4" FLG
60x66
725
82†
80
72
89
6300
10100
(1) for complete model number, suffix given
number by KW, elemnt designation letter (B=15KW, C=18KW,
D=20KW), voltage and pressure (e.g., ST24D-540C-480-150).
(2) Element removal clearance (R") is equal to 2 times the
element KW. NOTE: Required bgoth ends on "D"
models; left end only on "S" models. †Length of
control panel may exceed this dimension. (3) Ad 30"
to "L" for Jumbo Tanks (Desirable for cyclic loads).