1. General
The Thermal Storage System, "THERMOGENETIC" unit by PRECISION Boilers,
Model Number _______to provide space heating and/or domestic hot
water, as shown on the drawings, shall be furnished and installed by
the mechanical contractor. The system shall have a storage section of
______gallons with______KW electrical input as scheduled. The unit
shall be UL listed and manufactured by PRECISION, Morristown,
Tennessee.
The System shall be completely factory packaged, prewired and
pre-piped, with a sealed Thermal Storage section, balancing chamber,
mixing valves, heat exchangers, electric control panel, electric
immersion heating elements, pressure and temperature controls, ASME
approved relief valve, fill and drain connections, and other required
accessories.
2. Balancing Chamber
There shall be no permanent make up water connection to the Thermal
Storage section, and it shall be designed to store hot water up to a
maximum of___________F at________PSIG. The unit shall be capable of
delivering hot water in the design quantities and at the desired
temperature when the storage vessel is at the highest as well as the
lowest allowable temperature without water hammer.
3. Thermal Storage System Construction
The Thermal Storage section shall be fabricated of welded steel and
shall meet the requirements of the appropriate sections of the ASME
Code for 75 PSI design pressure. It shall have an overall diameter of
_____", an overall height of _____", and an overall length of ____".
The vessel shall be registered with the National Board, and an ASME
Data Report shall be furnished.
The vessel section shall be insulated with a minimum of 4 inches of 6
pound density mineral wool fiber insulation with sheet aluminum
jacketing. The standby heat loss shall be no more than 3.5 watts/sq.
ft. at an ambient temperature of 80 degrees F. The Storage section
shall be (Vertical), (Horizontal) and shall be supported by integrally
welded support saddles and perimeter frame. Steel lifting lugs are to
be welded to the shell and shall not protrude above the metal jacket.
3.1. Optional—Outdoor Application
Unit shall be constructed for outdoor application completely sealed
and weather tight, including a fully lighted and ventilated walk-in
service room with full size lockable access door. Room shall be an
integral part of the system covering all operating components. The
vessel for outdoor application shall be insulated with 6 pound density
mineral wool (6") (8") thick.
4. Heat Exchanger
The Thermal Storage section shall be equipped with a stainless steel
and copper heat exchanger sized to heat a flow of ____ GPM from
___degrees F to _____degrees F, with Thermal
Storage temperatures ranging from _____degrees F to _____degrees F.
The heat exchanger shall be designed for a maximum operating pressure
of 150 psi. The pressure drop of the heat exchanger section shall not
exceed _____ psi.
5. Electric Heating Elements
The electric heating elements shall be designed for a total of _____KW
at _____volts _____phase. They will be an integral part of the Thermal
Storage Section and be pre-wired to the electric control panel. The
electric heating elements shall be immersion type, pressure fitted to
a standard 150 PSI flange. Watt density shall not exceed 75 watts per
square inch.
6. Electric Control Cabinet
The pre-wired electric control cabinet shall have electric service
connection terminals, and shall include pressure, temperature and low
water controls, contactors, and fuses for each heating stage, and a
120-volt control circuit. The control cabinet shall include a disable
relay and a terminal strip mounted and factory wired to accept a load
limiting device to provide peak shaving. High temperature safety
controls shall shut off all electric heat input if the design
temperature is exceeded. All electrical components and wiring shall
conform to the National Electrical Code and be UL Listed.
7. Experience In Thermal Storage
The complete Thermal Storage System shall be factory assembled and
tested and shall require only service connections. The manufacturer of
this type of self-contained, integral Thermal Storage System must have
at least 20 installations that have been operating satisfactorily, at
above temperatures, for over five years. At time of equipment jobsite
setting, a representative of the manufacturer shall be present to
assure proper handling.
8. Factory Licensed Startup
Check, test and start-up shall be performed by a factory trained
service representative. Maintenance and operating instructions in
multiple copies shall be furnished in booklet form.