Products:
Deaerators: TR
Model TR Deaerator
Specification
Furnish and
install as one Tray Type Deaerating Heater as designed and
manufactured by Precision Boilers. Deaerator shall be model number
___________ and shall consist of the following:
(1)
Basic:
_____PPH Tray Type Deaerator with a capacity of _____ gallons to
overflow (______ minutes of storage). Storage vessel shall be ______
diameter by ______ shell length (not including heads) and shall be
constructed in accordance with the ASME code (latest revision).
Deaerator shall include connections as follows: water inlet ____,
steam inlet______, pump suction ______, overflow________, relief valve
and vacuum breaker (common)_______, vent ______, vessel drain
______,thermometer________, pressure gauge_______, 12” x 16” mainway
(minimum) and all water level instrumentation equalizing connections
required for operation (minimum of four). Each pump suction shall be
equipped with a vortex breaker which must be constructed as follows:
cross plate design of ¼” material and dimensionally two times greater
than the nozzle diameter (minimum). Deaerator shall operate at all
flows with a 20:1 turndown ratio, shall deaerated the water so that
the oxygen in the effluent leaving the deaerator storage tank shall
not exceed .005 cc/liter as determined by the Heat Exchange Institute
method, Winkler method, or any other leading testing method approved
by ASTM, and shall reduce the titratable free CO2 to zero as
determined by the APHA testing method. The Tray Deaerator shall have
spray valves which shall be #316 stainless steel, be non-binding, and
have a guide bar. Deaerator shall have an internal direct contact
vent condenser. Tray enclosure shall be #304 stainless steel with a
¼” minimum wear plate. Tray box will be equipped with a gliding tray
door system for ease of tray inspection and removal. Trays shall be
constructed of #430 stainless steel and shall be all riveted. No
welding of trays will be acceptable. Operation shall be of the
counterflow design; water shall enter vent condenser, go through spray
valves and cascade downward over trays while the steam will enter
through the bottom of tray box, moving upwards through the trays. The
result of the counterflow operation will be fully Deaerated Water
exiting the tray section and spilling into the storage section..
(2) Operating Conditions:
Returns: Low
Temp (<227º F) _____%@_____ ºF
High Temp (>227º F) _____%@_____
ºF
Make-Up: _____PSIG _____%@_____ ºF
(3) System Components:
Other integral and necessary components shall be per specification and
shall include instruments (sight, temperature and pressure gauges, and
level and pressure controls); level control valve (mechanical,
electric, electro-pneumatic, pneumatic); feedpump(s) (turbine,
multi-stage centrifugal, etc.); overflow drainer; vacuum breaker;
relief valve (sentinel or full capacity); pump suction stop valve,
strainer and vibration isolator; pump discharge stop valve, check
valve, bypass orifice or relief valve, pressure gauge, etc.;
NEMA____UL-Labeled control cabinet to include necessary pilot lights,
switches, control transformer, disconnects, starters, logic relays,
etc.
Specifications subject to change without notice.
|
   
|
|