Products:
Unfired: USG
Model USG Unfired Steam Generator
Steam to Steam
Specification
Furnish and install as shown on the plans
Unfired Steam Generator(s) fabricated per these specifications,
including all accessories and construction features as described
herein. Generator(s) shall be (vertical) (horizontal) configured, be
fabricated of (carbon steel) (300 Series Stainless Steel), and be
completely Factory assembled and pre-tested prior to shipment.
Generator(s) shall include an ASME Section VIII pressure vessel
which has been fabricated under inspection by an authorized
inspector holding a National Board Commission and subsequently
stamped and National Board Registered.
Steam Generator(s) shall be PRECISION Model No.
USG___________________. The Generator(s) shall be designed to
operate at ________ PSI and shall produce ___________ lbs steam/hr
(from and at 212° F) when provided with ________ PSI steam at the
control valve.
The Generator pressure vessel and all trim shall be as set forth in
the ASME Code, including ASME-stamped safety valve(s) to relieve
full capacity of the steam control valve. The pressure vessel shall
be constructed of (carbon steel) (stainless steel) for ________ psig
ASME Code design. The pressure vessel shall be housed in a 16-gauge
steel enclosure and insulated with 3 inches of ¾ pound-density
fiberglass insulation. The vessel and controls shall be mounted on a
common steel structural base.
The tube bundle heating coil shall be ASME constructed of ¾ x 20 BWG
(copper) (stainless steel) tubing with a nonferrous tube sheet. The
heating coil shall be installed in the tank by bolted connection to
the collar flange and tube head.
Bundle side controls shall include a (self operating) (pneumatic)
steam pressure controller and control valve (NC Fail Safe) and
required trim including steam strainer, main float thermostatic
steam trap, and auxiliary drip trap.
Tank-side controls shall be (bronze) (stainless steel) and shall
include safety valve(s), level / pump control, sight gauge, level
control drain valve, blowdown valve, pressure gauge, and surface
blowoff connection. Optional trim shall include low water switch,
high pressure switches, safety steam supply cutoff, low pressure
switch, audible alarm circuit, feedwater solenoid valve. and
automatic surface blowoff.
|
   
|
|
|
|